Olie Pot Controller

Teknisk data: HBOR/C

The HBOR/C sensor detects oil in liquid ammonia like the HBSR switch but has additional functionality. It can control a valve for filling or emptying the container to maintain the level. The built-in controller can be configured with the parameters necessary for direct control of a solenoid valve for oil level control.

The oil detection is done indirectly by detecting both liquid ammonia and gas. This way of detecting secures that the sensor can return oil in ammonia systems without the risk of both liquid ammonia and gas being emitted.

HBOR is typically used in oil pots, receivers, and oil collectors in evaporators, where you like to detect and return the oil to the compressor or oil reservoir. The switch can be used at low temperatures.

Shop image

Product features

  Robust og pålideligt design med solid state udgang.
Designet til køleindustrien - max tryk op til 100 bar.
Tydelig LED indikation ved væskedetekterring.
Split design hvilket gør sensoren nemt at montere og servicere. Elektronikken kan adskilles fra den mekaniske del ved at løsne 2 pinolskruer.
Automatisk styring af magnetventiler til aftømning af olie.
PC programmerbar tidsstyring afhængig af olie pottens størrelse.

Applications

HBOR

Specifications

Tilslutningsdiagram

 HBOC C HBOR C diagram 003 Small

Tegning

HBOR dimensions 

Power supply
Voltage24 V DC +/- 10%
Current consumptionMax 30 mA
Plug connectionM12, 5 pins
Direct valve control - cable
Solenoid valve24 V DC - max 24 W
Cable length3 m (118”)
Cable dimensions2 x 0,75 mm2
M12 output
Alarm outputSolid State
Contact functionNC/NO
Potential free outputMax 1 A (24W)
Environmental conditions
Ambient temperature-30...+50°C
Refrigerant temperature-60...+80°C*
Max pressure100 bar
Protection degreeIP54
VibrationsIEC 68-2-6 (4g)
Mechanical specifications
Thread connection1/2" and 3/4”
Material - liquid partsAISI 304 / PTFE
Material- electronic partsNylon 6 (PA)
Dimensions210x52x40
Weight300 g
House designAngle housing
Approvals
EMC testEN 61000-2
Indication
Power, oilfeed and alarmLED (green, yellow & red)
LED indication of switch pointGreen
Configuration
ConfigurationWith PC tool
Accessories
USB programming cableHBxC-USB

Ordering code

OutputThread typeOrdering code
NC1/2" NPTHBOR/C-1
NC3/4" NPTHBOR/C-2
NC1/2" BSPPHBOR/C-5
NC3/4" BSPPHBOR/C-6
Electronic part for HBOR/C HBOR/C-EL