Temperature Sensor

Technical data: HBTS

HBTS is a temperature sensor in accordance with DIN 60751, and it is available in two variants, PT100 and PT1000 – DIN B – class 3. The sensor is designed for the refrigeration industry where servicing of the electronics can be carried out without emptying the system of refrigerant. The sensor is delivered with a 60 & 90 mm sensor element length and a 6 mm sensor diameter. Sensor well is included with the sensor.

Shop image

Product features

  4-wire PT100 orr PT1000 sensor element DIN B class 1/3 - DIN 60751 
Refrigeration industry design - max pressure 150 bar.
Temperature area: -50..+130°C
M12 plug connection - DIN 0627

Applications

HBPS HBTS application web

Specifications

Connection diagram

HBTS tilslutning 

Drawing

HBTS 60 w 

HBTS-xxx/xx-60

HBTS 90 w

HBTS-xxx/xx-90

Electrical connection
PlugM12-DIN 0627 
Sensor elementPT100 / PT1000 
Sensor classDIN B - kl. 1/3 
Sensor design4 wire
Environmental conditions
Ambient temperature-30...+85°C
Refrigerant temperature-50...+130°C*
Max pressure150 bar 
Protection degreeIP67
VibrationsIEC 68-2-6 (4g)
Mechanical specifications
Thread connection1/4” NPT or BSPP
Material - liquid partsAISI 304 
Material - electrical parts Plast 
Sensor elementØ6 - 60 / 90 mm 
Approvals
EMC testEN 61000-2

Ordering code

Sensor typeSensor lengthThread typeOrdering code
PT10060 mm1/4" NPT HBTS-PT100/NPT/60
PT100 90 mm1/4" NPT HBTS-PT100/NPT/90
PT100 60 mm1/4" BSPP HBTS-PT100/BSP/60 
PT100 90 mm1/4" BSPP HBTS-PT100/BSP/90 
PT1000 60 mm1/4" NPT HBTS-PT1000/NPT/60 
PT1000 90 mm1/4" NPT HBTS-PT1000/NPT/90 
PT1000 60 mm1/4" BSPP HBTS-PT1000/BSP/60
PT1000 90 mm1/4" BSPP HBTS-PT1000/BSP/90