Refrigerant Switch - 90..240 V AC

Technical data: HBSR-SSR-2

HBSR-SSR-2 is a level switch for the detection of NH3 and Brine refrigerants.

Typically it is installed on the refrigerant vessels, pump separators, economisers or heat exchanger.

The sensor is specially built to resist high pressure and low temperatures.

It has universal power supply 90...240 V AC - 50/60 Hz.

Product features

Proven sensor technology with solid state output contact function NO or NC.
Designed for the industrial refrigeration industry - max pressure 100 bar.
Universal power supply 90...240 V AC - 50/60 Hz.
Clear indication with LED when refrigerant is detected.
Split design which makes it easy to install and make diagnostic on. The electronic part can be easily disconnected by 2 screws.

Applications

 HBSR-HV

Specifications

Connection diagram

HBSR SSR web

 

Drawing

HBSR SSR Maalsat 

Power supply
Voltage90...240 V AC
Max. current consumption40 W
Plug connectionM12 - DIN 0627
Output
Output typeSolid State Relay
Contact functionNC or NO
Environmental conditions
Ambient temperature-30...+50°C
Refrigerant temperature-30...+80°C
Max pressure100 bar
Protection degreeIP65
VibrationsIEC 68-2-6 (4g)
Mechanical specifications
Thread connection3/4”
Material - liquid partsAISI 304 / PTFE
Material- electronic partsNylon 6 (PA)
Dimensions193 x52x40
Weightn/a
House designFront
Approvals
EMC testEN 61000-2

Ordering code

OutputThread typeOrdering code
Solid state relay - NO3/4" NPTHBSR-SSR-2/NO-2
Solid state relay - NO3/4" BSPPHBSR-SSR-2/NO-6
Solid state relay - NC3/4" NPTHBSR-SSR-2/NC-2
Solid state relay - NC3/4" BSPPHBSR-SRR-2/NC-6
Spare parts for HBSR-SSR-2
Electronic part for HBSR-SSR-2/NO HBSR-SSR-2/NO-EL
Electronic part for HBSR-SSR-2/NC HBSR-SSR-2/NC-EL