Oil Return Switch for NH3 systems
Output: NPN, Contact function: NC
3/4" NPT - w. set screw connection IP54
Itemnumber: HBOR-NPN/NC-2
Output: NPN, Contact function: NC
3/4" NPT - w. set screw connection IP54
Itemnumber: HBOR-NPN/NC-2
To view our prices you must be logged in. Please log in or contact info@hbproducts.dk.
You can still collect items in your basket and send a request.
The HBOR is a Level Switch designed for automatic oil return in ammonia refrigeration systems. This sensor detects the difference between refrigerant and oil, ensuring that when oil is drained and ammonia surrounds the sensor, the drain valve closes without risking ammonia leaks. It is typically used for oil return and discharge in components such as evaporators, receivers, and oil pots, primarily on the low-pressure side of the system.
- Liquid temperature range: Operate across a temperature range of -30°C to 80°C (-22°F to 176°F).
- Pressure tolerance: Rated for pressures up to 100 bar (1450 psi).
- Power supply: The switch operates on a 24V AC/DC power supply.
- Split design: Simplifies installation and diagnostics; electronic parts can be removed with two screws.
- LED indicators: Features a clear LED indicator to signal when oil is detected.
| Document list | |
| Data Sheet I HBOC And HBOR | 396.00 Kb |
| Switches Circular Electronic Instruction Manual | 892.00 Kb |
| Switches Circular Electronic Quick Guide | 702.00 Kb |
Product specs at a glance
| Liquid group | Oil |
| IP Class | IP54 |
| Power Supply | 24V AC/DC |
| Thread | 3/4" NPT |
| Output | NPN |
| Fluid temp. | -40 to 80°C (-40 to 176°F) |
| Ex/ATEX approved | No |
Check the document library
Dive into the library for more documatation material