Vapor Quality Control Sensor for CO2 (With Control Function)

                                                                                                

zero superheat control                                                CO2 READY                          

   SAVINGS                                                        

New Sensor Technology Controls the Phase of Refrigerant as Vapor Quality

Technical data: 

HBX-DX-XXX-CU | HBX-DX-XXX-SS

HBX-DX Vapor Quality Sensor/Control is a new sensor solution for optimizing Evaporator Control to Zero Superheat. The ”X”-sensor measures the phase of refrigerant and Vapor Quality as degree of dryness. The electronical part is fully separated from the sensors mechanical part and can be replaced without interference with the pressure side. The sensor is installed in the outlet of the evaporator, as part of the suction line. The soldering connections, fittings and pipes are all made of high pressure copper type K65 in CU-version and in stainless steel for SS-version. Setting for commonly used refrigerant types, CO2, Hydrocarbons, HFO’s and HFC’s is possible via special software.

 HBX-DX-XXX-CU: Vapor Quality measurement and PI control with integrated stepper motor driver or PWM control or modulating 4-20mA for electronic expansion valves.

Product features

Semi Flooded evaporator operation ensures optimal heat transfer at all loads
Increased evaporation pressure/temperature
Lower discharge temperature
Optimal performance in all climates
Compressor protection

Applications

HBX DX XXX T APPLICATIONS 1 WEB

HBX DX XXX T APPLICATIONS 2

 

 HBX DX XXX T Fordamperkasse Kobber3

Specifications

Connection Diagram

HBX DX XXX CU T ELECTRICAL CONNECTION

Drawing

HBX DX XXX CU DIMENSIONER          HBX DX CU XXX FIL 2294 DIMENSIONSTEGNING  

Power supply
Voltage24V AC/DC
Current consumption250 mA with heater
Electronic connectionM12, 5 p
Output
Output signal ”X” 0.8 to 1.04-20 mA / 0-10 V
Valve output, S or C or PWMStepper motor, mA, PWM
Environmental conditions
Ambient temperature-40...+50°C
Refrigerant temperature-55...+50°C
Max. pressureMax 120 bar
VibrationsIEC 68-2-6 (4G)
Mechanical specifications
Thread connectionsPlease see drawing
SizePlease see drawing
MaterialCU K65, SS304, PA6
House typeFront
Approvals
EMCEN 61000-2

Ordering code

DesignLength / threadConnectionValve typeCable to valveOrdering code
In-lineX1=243, X2=140, X3=110 mm3/8"For direct operation of modulating valve Yes HBX-DX/C-CU-3/8"
In-lineX1=243, X2=140, X3=110 mm1/2"For direct operation of modulating valve Yes HBX-DX/C-CU-1/2"
In-lineX1=246, X2=145, X3=112 mm5/8"For direct operation of modulating valve Yes HBX-DX/C-CU-5/8"
In-lineX1=246, X2=145, X3=113 mm3/4"For direct operation of modulating valve Yes HBX-DX/C-CU-3/4"
In-lineX1=248, X2=150, X3=113 mm7/8"For direct operation of modulating valve Yes HBX-DX/C-CU-7/8"
In-lineX1=251, X2=160, X3=118 mm1 1/8"For direct operation of modulating valve Yes HBX-DX/C-CU-1 1/8"
In-lineSpare partElectronic Part for HBX-DX/C-XX YesHBX-DX/C/T-EL
In-lineX1=243, X2=140, X3=110 mm3/8"For direct operation of modulating valve Yes HBX-DX/C-SS-3/8"
In-lineX1=243, X2=140, X3=110 mm1/2"For direct operation of modulating valve Yes HBX-DX/C-SS-1/2"
In-lineX1=246, X2=145, X3=112 mm5/8"For direct operation of modulating valve Yes HBX-DX/C-SS-5/8"
In-lineX1=246, X2=145, X3=113 mm3/4"For direct operation of modulating valve Yes HBX-DX/C-SS-3/4"
In-lineX1=248, X2=150, X3=113 mm7/8"For direct operation of modulating valve Yes HBX-DX/C-SS-7/8"
In-lineX1=251, X2=160, X3=118 mm1 1/8"For direct operation of modulating valve Yes HBX-DX/C-SS-1 1/8"
In-lineSpare partElectronic Part for HBX-DX/C-XX Yes HBX-DX/C/T-EL
In-lineX1=243, X2=140, X3=110 mm3/8"For direct operation of stepper motor Yes HBX-DX/S-CU-3/8"
In-lineX1=243, X2=140, X3=110 mm1/2"For direct operation of stepper motor Yes HBX-DX/S-CU-1/2"
In-lineX1=246, X2=145, X3=112 mm5/8"For direct operation of stepper motor Yes HBX-DX/S-CU-5/8"
In-lineX1=246, X2=145, X3=113 mm3/4"For direct operation of stepper motor Yes HBX-DX/S-CU-3/4"
In-lineX1=248, X2=150, X3=113 mm7/8"For direct operation of stepper motor Yes HBX-DX/S-CU-7/8"
In-lineX1=251, X2=160, X3=118 mm1 1/8"For direct operation of stepper motor Yes HBX-DX/S-CU-1 1/8
In-lineSpare partElectronic Part for HBX-DX/S-XX Yes HBX-DX/S/T-EL
In-lineX1=243, X2=140, X3=110 mm3/8"For direct operation of stepper motor Yes HBX-DX/S-SS-3/8"
In-lineX1=243, X2=140, X3=110 mm1/2"For direct operation of stepper motor Yes HBX-DX/S-SS-1/2"
In-lineX1=246, X2=145, X3=112 mm5/8"For direct operation of stepper motor Yes HBX-DX/S-SS-5/8"
In-lineX1=246, X2=145, X3=113 mm3/4"For direct operation of stepper motor Yes HBX-DX/S-SS-3/4"
In-lineX1=248, X2=150, X3=113 mm7/8"For direct operation of stepper motor Yes HBX-DX/S-SS-7/8"
In-lineX1=251, X2=160, X3=118 mm1 1/8"For direct operation of stepper motor Yes HBX-DX/S-SS-1 1/8"
In-lineSpare partElectronic Part for HBX-DX/S-XX Yes HBX-DX/S/T-EL
In-lineX1=243, X2=140, X3=110 mm3/8"Special PWM-configuration with cable Yes HBX-DX/PWM-CU-3/8"
In-lineX1=243, X2=140, X3=110 mm1/2"Special PWM-configuration with cable Yes HBX-DX/PWM-CU-1/2"
In-lineX1=246, X2=145, X3=112 mm5/8"Special PWM-configuration with cable Yes HBX-DX/PWM-CU-5/8"
In-lineX1=246, X2=145, X3=113 mm3/4"Special PWM-configuration with cable Yes HBX-DX/PWM-CU-3/4"
In-lineX1=248, X2=150, X3=113 mm7/8"Special PWM-configuration with cable Yes HBX-DX/PWM-CU-7/8"
In-lineX1=251, X2=160, X3=118 mm1 1/8"Special PWM-configuration with cable Yes HBX-DX/PWM-CU-1 1/8"
In-lineSpare partElectronic Part for HBX-DX/PWM-XX Yes HBX-DX/PWM/T-EL
In-lineX1=243, X2=140, X3=110 mm3/8"Special PWM-configuration with cable Yes HBX-DX/PWM-SS-3/8"
In-lineX1=243, X2=140, X3=110 mm1/2"Special PWM-configuration with cable Yes HBX-DX/PWM-SS-1/2"
In-lineX1=246, X2=145, X3=112 mm5/8"Special PWM-configuration with cable Yes HBX-DX/PWM-SS-5/8"
In-lineX1=246, X2=145, X3=113 mm3/4"Special PWM-configuration with cable Yes HBX-DX/PWM-SS-3/4"
In-lineX1=248, X2=150, X3=113 mm7/8"Special PWM-configuration with cable Yes HBX-DX/PWM-SS-7/8"
In-lineX1=251, X2=160, X3=118 mm1 1/8"Special PWM-configuration with cable Yes HBX-DX/PWM-SS-1 1/8"
In-lineSpare partElectronic Part For HBX-DX/PWM-XX Yes HBX-DX/PWM/T-EL

Downloads